Click to go to Home page


Myron L Company News Release


Myron L Company introduces two new 720 Series II Monitor/controllers

pH and ORP Monitor/controllers measure water quality for a variety of applications

 

Carlsbad, Ca. March 29, 2002: The Myron L Company introduces two new members to our Monitor/controller family. The 720 Series II pH and ORP Monitor/controllers measure pH or Oxidation- Reduction Potential/Redox in applications such as reverse osmosis, process control, seawater desalination, waste treatment and more. 

The advanced "isolated" circuitry of the 720 Series II pH/ORP Monitor/controllers ensures continuous, accurate and reliable measurements. This circuitry also eliminates ground loop issues associated with non-isolated circuitry.  The unique sensor preamp allows for longer distances between the sensor and the Monitor/controller without the loss of accuracy or reliability.

Additional Monitor/Controller Features:

The pH and ORP Monitor/controllers have built-in electronic calibration, which allow for fast quality checks without buffers.

A push-to-test button makes set point checks easy, while the internal alarm set discourages unauthorized adjustments.

Standard on all Myron L Monitor/controllers is a heavy-duty 10-amp output relay, operating on either increasing or decreasing readings.  Bright green and red LEDs indicate above or below set point readings.

All 720 Series
II models feature an IP64/NEMA 3 splash and corrosion-proof rated enclosure.  Compact in size, 6 x 4.8 inches (152 x 122 mm), the 720 Series II models are suitable for panel, bench or surface mounting.


pH/ORP Sensors:

In conjunction with the 720 Series
II pH/ORP Monitor/controllers, the highly accurate pH or ORP sensors utilize a pre-amplifier to ensure stability over a long distance, eliminate potential noise problems and ensure accurate, repeatable readings. These reliable sensors also feature an integral temperature sensor to ensure exact, rapid and automatic temperature compensation (pH). Several sensor models are available to meet a variety of applications and service environments.

Founded in 1957, the Myron L Company has played an important role in the water instrumentation industry for over 35 years. One of the world's leaders in water quality instruments, Myron L manufactures a comprehensive line of high quality hand-held and inline instruments that measure a wide variety of water quality parameters: conductivity, resistivity, TDS, pH, ORP and temperature.  Myron L instruments are accurate, reliable, simple to operate and can be used in municipal, commercial and industrial applications.

With the ever increasing demand for quality water, the Myron L Company, throughout its extensive distributor network, supplies water professionals worldwide.  Contact your local distributor or visit us at www.myronl.com.


720 Series
II pH and ORP Monitor/Controller Specifications:

Range:  0 - 14 pH or ±2000 mV ORP

Display:  Analog Models: 2 1/2" (63 mm) Meter
Digital Models: 1/2" (13mm) 3 1/2 Digit LCD; opt. 3 1/2 Digital Backlit

Linearity:  Electronics: ±0.05% (±0.01 pH units / ±1 mV of full scale)

Resolution:  Digital Display: ±0.01 pH units / ±1 mV
Analog Meter: ±0.13 pH units / ±40 mV

Sensitivity:  0.05% of full scale (0.01 pH units / 1.0 mV)

Stability:  ±0.05% of full scale (±0.01 pH units / ±1.0 mV)

Repeatability:  ±0.05% of full scale (±0.01 pH units / ±1.0 mV)

Calibration Check:  Built in (7 & 0 pH / 0 & -2000 mV)

Recorder Output:  Isolated 0 - 10 VDC @ 5 mA max. (linear); standard on all models

Output Impedance:  100W ±5%

Sensor Input:  One; 3-input option available (pH & ORP sensors may NOT be mixed).

Control Function:  Single Alarm/controller fully adjustable 0-100% of full scale
Hysteresis: Adjustable from 0.3—3% of full scale
Indicators: Above (red) and below (green) set point LEDs (reversible)
Contact Rating: SPDT 10 amp @ 250 VAC, 30 VDC. Relay operates increasing or decreasing reading (selectable)

Second Alarm/Controller, with above specifications–optional

Solid State Output:  Powered; 24 VDC Unregulated 30 mA max.

Power:  115/230 VAC, 50/60 Hz, ±15% (user selectable)

Maximum Power Consumption:  @ 115 V: 100 milliamps

Dimensions:  6" (152 mm) H x 4.8" (122 mm) W x 3.8" (96 mm) D

Construction:  Fully gasketed heavy-duty ABS case; splash & corrosion proof IP64/NEMA 3 rated

Ambient Temperature Range:  32°F to 140°F (0°C to 60°C)

Weight:  2 lbs. (0.9 kg)
 

 

 